What Size Wire To Use For Meter Socket Box

When installing a 200 amp electrical service, y'all demand to be certain you use the right gauge wire. You'll need a permit to practise the professional installation. Many areas withal allow homeowners to obtain their permits. You'll demand to check with your local building section to know if you can get the permit or if you lot'll need the help of an electrician.

Installation of 200 amp electrical service needs a #2/0 AWG copper wire or #4/0 AWG for aluminum or copper-clad wire inside a minimum of 1.v inches, schedule twoscore or 80 PVC conduit for underground service. However, 2 or ii.5 inches is recommended if running 3 wires in the same conduit.

Wiring 200 amp service requires an electric permit and professional installation by a qualified electrician in accordance with local electric codes.

Ability is received from the utility service lines and flows through the exterior electrical meter base and into the main electrical panel in an fastened garage, basement, or interior room.

Wire Sizes for 200 Amp Service

AWG, American Wire Judge, is the Us standard for sizing electrical wiring.

Wiring a 200 amp feeder requires either #ii/0 copper wiring or #4/0 aluminum or copper-clad wiring. Which wire is used is determined by the voltage driblet and length of the wiring.

The following table reflects wiring size, length, and voltage drop:

Service or Feeder Rating Copper Wire Aluminum or
Copper-Clad Aluminum Wire
Minimum Conduit Size
100 Amps #4 AWG #two AWG 1.25 inch
110 Amps #three AWG #one AWG one.25 inch
125 Amps #2 AWG #1/0 AWG 1.25 inch
150 Amps #1 AWG #2/0 AWG 1.25 inch
175 Amps #1/0 AWG #3/0 AWG 1.v inch
200 Amps #ii/0 AWG #four/0 AWG i.5 inch
225 Amps #3/0 AWG 250 kcmil i.5 inch
250 Amps #4/0 AWG 300 kcmil 2 inch
300 Amps 250 kcmil 350 kcmil 2.5 inch
350 Amps 350 kcmil 500 kcmil iii inch
400 Amps 400 kcmil 600 kcmil three inch
Source: National Electrical Code

Many electrical contractors opt to use #iv/0 aluminum or copper-clad wire.

For copper conductors, you'll demand a #2/0 AWG copper wire usually used for electrical wiring considering it is more heat resistant than aluminum. Copper won't rust and is resistant to oxidation.

For aluminum or copper-clad aluminum wiring, you lot'll need #4/0 AWG aluminum wiring. Aluminum wiring requires a larger diameter wire because it has a lower conductivity than copper. Aluminum wiring requires an antioxidant coating at the connection terminals to resist corrosion. Copper-clad aluminum doesn't require an antioxidant coating at the connectedness terminals.

Aluminum wirings appeal widespread because it costs less, is lightweight, and is more than flexible than copper, even though copper is considered a improve conductor.

Why Copper Wiring is Preferred over Aluminum

Electricians and homeowners alike prefer copper wiring, especially for branch circuits. Copper wiring has many benefits, including:

  • Electrical conductivity: Copper wire is a highly conductive metal, 2nd simply to silver. Copper can handle a college electrical load, so you tin employ a smaller guess wire. In fact, copper wire is well-nigh one-half the diameter of aluminum wire for the same conductivity.
  • Heat Resistant: Copper wire conductive properties make the wire more than heat resistant than aluminum wire. Copper wire does not aggrandize and contract like aluminum which means the wire connections remain tight on lugs.
  • Corrosion Resistant: Copper is resistant to corrosion. Patina is a green-tarnish that changes the outer color of copper. Patina forms by oxidation, however, practise not bear on the conductivity.
  • Malleability: Because copper is highly conductive, the wire strands are thinner, making the wire more malleable without the risk of breaking.
  • Distance: Copper conductors tin can be used over longer distances due to its highly conductive properties and estrus resistance.

Pros of Aluminum or Copper-Clad Aluminum Wire

Nosotros simply discussed why copper is preferred; however, copper-clad and aluminum wire sizes are more popular on service entry wire for several reasons, including:

  • Budget-Friendly: Aluminum wire is preferred due to its lower cost. Aluminum conductors are cheaper to produce compared to copper conductors. Aluminum copper-clad is ameliorate but does cost more than than aluminum wiring. Aluminum costs much less than copper-clad and copper wires.
  • Faster Installation: Aluminum is lighter than copper and very malleable for its larger wire gauge. Electricians discover is easy to work because is lightweight and feeds well through the electrical conduit which makes for faster installation and lowers textile and labor costs.

Aluminum wiring expands and contracts with estrus which causes the wire connectedness to loosen over time, raising the risk of an electrical fire. Aluminum service wiring is a group of smaller solid aluminum strands rather than ane solid wire, making the aluminum wire safety to use in residential homes.

The Length Your Service Wire Runs Matters

When computing wire size, you demand to know how far the service entrance wires will run from the electrical meter base to the electrical panel. The maximum voltage driblet (we will discuss shortly) allowed is three%. The distance your service entry wire needs to travel will determine whether y'all utilise aluminum or copper wire and gauge necessary.

Service Wire Size Maximum Distance
Copper #2/0 Wire 50 feet
Copper #three/0 Wire 100 feet
Copper #4/0 Wire 150 feet
Aluminum #four/0 Wire 50 feet
Aluminum 300 kcmil 100 feet
Distances may vary by location. Check with your local edifice department for requirements.

You tin utilise aluminum and copper for a 200 amp service entry wire. Nonetheless, the aluminum gauge will be higher due to its reduced conductivity and heat resistance properties. You can use copper wire over a longer distance.

What is Voltage Drib?

Voltage drop is the loss of voltage that occurs over the wire due to natural resistance. The longer a wire runs, the more voltage loss that occurs. The size wire gauge has to increase to offset the voltage drop.

The voltage at the circuit breaker should exist 120 volts. Using a voltage meter, take a reading at the appliance or the farthest device. Ideally, you should not have a voltage drop higher than 3%. For a 120-volt electrical circuit, the voltage drib should be no less than 117 volts. Likewise, on 233 volts on a 240-volt electric circuit.

How Many Wires You lot Need for 200 amp Service

The type of wire you demand will vary depending on your electrical system. The run from the meter base to the main disconnect box or main panel is 3-wire, consisting of two hot wires and ane neutral wire. The neural and basis bars take electrical bonding connecting the confined.

The feeder run from the main electrical panel to the interior distribution panel (subpanel) is 4-wire, consisting of two hot wires, 1 neutral wire, and 1 basis wire. Yous don't bond the neutral and basis bars inside subpanels.

What Size Conduit Yous Need for 200 Amp Service

An electrical panel has knockouts for connecting electrical feeder conduit. You lot can use either a 2-inch or two.five-inch conduit based on the fill up space you lot intend to occupy inside the conduit. If 3 or more wires are inside the conduit, the maximum fill infinite of 40%.

In Chapter nine, Table 5A of the 2017 NEC, a #iv/0 Aluminum stranded conductor takes upwards 176.3mm2 of fill up infinite. If you lot multiply 176.3mm2 by 4 gives you a total of 705.2mmii of fill space used past the entire feeder.

According to Affiliate nine, Table 4 of the 2017 NEC, a 2″, Schedule fourscore PVC conduit has 742mm2 usable fill.

So, a 2″ conduit will suffice, or you can upsize to 2.5″ if you lot wish for ease of pulling. Keep in heed that the area of the wires must be less than 40% of the internal space of the pipage when iii or more than wires are present.

What Size Ground Wire for 200 Amp Service

The NEC is the electric code used in the U.s.. The minimum size for a grounding wire for 200 amp is #4 AWG copper or #2 AWG aluminum, according to Article 250 of the 2020 NEC.

The size of the principal usher may need to increment for a multifariousness of reasons, including the length of the run, available fault current, or any number of reasons. The NEC is a safety guide. Local municipalities set and adopt code guidelines. Call a local electrician or your urban center for specific guidelines.

GROUNDING ELECTRODE Usher SIZING (Tabular array 250.66)

Size of Main Panel Copper Conductors Aluminum or Copper-Clad Aluminum
125 Amps #8 AWG #half dozen AWG
150 Amps #6 AWG #iv AWG
200 Amps #4 AWG #2 AWG

What Size Ground Rod for 200 Amp Service

A ground rod needs to be at least five/eight″ (0.625) in diameter and at to the lowest degree 8 to 10 anxiety long with a clench and the appropriate ground wire. The ground rod needs to be driven 8 feet deep into the footing and cut dorsum shut to the ground. The wire and clench are secured tightly to the top of the ground rod.

Where there is a lot of electricity in the ground, a thicker #3 size wire may exist required. Two ground rods are necessary for regions where soil electrical resistance is high because of new code requirements.

Use the correct type of grounding rod. Pipe or rebar can likewise exist used for grounding. The grounding rod must be galvanized steel and should be at least eight feet long.

How Many Footing Rods for 200 Amp Service

A ground rod that does not meet the NEC's 25 OHMS or less requirement necessitates using a second ground rod, with the ground rods being at least 6′ autonomously.

You install a ground rod for a organization, and the first ground rod has a resistance of 25 ohms or more. According to the NEC, you must install a second grounding rod. On the other mitt, many contractors do not take footing resistance into business relationship. They anticipate driving two basis rods to satisfy 250.56's standards regardless of actual ground resistance. As a result, two ground rod connections are typical but aren't always necessary.

The NEC article 250.53(B) requires yous to infinite grounding rods at least vi feet autonomously connecting past a grounding wire. Even so, this spacing is a minimum. When using the typical 8-foot or 10-foot ground rod, y'all get the all-time results by spacing them at least xvi or 20 anxiety apart, much further than the minimum 6-foot spacing.

Check Local Electrical Codes & Permit Requirements

Electric codes are ready past the National Electric Code (NEC) only tin vary by location. Using a qualified electrician ensures your 200 amp electric service meets local codes and allow requirements.

The 200 amp size wire referred to in this article is from the NEC code and may vary from your local building lawmaking. Your local lawmaking will prefer or alter the NEC codes to fit their requirements.

Before the utility service can connect power to the business firm, you'll need a Certificate of Occupancy (CO). The let allows for a final inspection to connect the electrical service. The CO is issued after the electrical work has passed the building inspection.

200 Amp Electrical Service Installation Costs

Information technology's nearly impossible to accurately price the toll of installing a 200 amp entry service in a house. Nosotros demand to consider numerous factors, like location, the amount of work required, and textile costs in your area. Installing a 200 amp electrical service typically includes installing a 200 amp service wire, conduit, meter base, and a 200 amp electric panel.

Based on HomeAdvisor.com, the national average price of a complete 200 amp electric installation costs $one,900 to $7,250, with average costs of $four,650, includes the following:

  • 200 Amp Service Panel: Average price ranges from $750 to $2000, with a median cost of $1375.
  • 200 Amp Meter Base: Average cost ranges from $150 to $400, with a median cost of $275.
  • 200 Amp Service Wire: Average cost ranges from $1000 to $v,000, with a median cost of $3,000.

According to MidPenn Electric, a leading electric contractor in Pennsylvania, "a new 200 amp service can price anywhere from $4,200 to $five,000". Therefore, the HomeAdvisor toll averages seem to be reasonably authentic.

Decision

Installing 200 amp wire is not a DIY project for homeowners. Wiring a 200 amp panel is a big project that requires the services of a qualified and certified electrician. Yous may require a permit to install a 200 amp service. The electric service will demand to be disconnected entirely in existing homes to install the 200 amp service.

Also, see our guide, Wire Size for 100 Amp Electric Service.

What Size Wire To Use For Meter Socket Box,

Source: https://homeinspectioninsider.com/200-amp-service-wire/